Section
|
Notes
|
Mechanical
|
§110.2
|
Space conditioning equipment, updated efficiencies to align with ASHRA 90.1-2016
|
§110.5
|
Pilot lights prohibited: Prohibits continuously burning pilot light for indoor and outdoor fireplaces.
|
§120.1
|
Ventilation systems requirements are broken out by building type:
- ·§120.1 (b) high rise residential (ASHRAE 62.2)
§120.1 (c) nonresidential, hotel/motel (ASHRAE 62.1)
|
§120.1
|
- Filtration required for central space conditioning systems and supply side of ventilation systems.
- MERV 13 filter efficiency required.
|
§120.1(b)1
|
High-rise residential air filtration:
Filters for space conditioning systems:
- 2” depth filter: allowable pressure-drop determined by the system designer
- 1” filter if sized according to equation 120.1-A with maximum pressure drop of 0.1” of water
|
§120.1(b)1
|
High-rise residential air filtration:
Filters for ventilation systems:
- System must be designed to accommodate the filter pressure drop determined by the system designer
- Filters must be labeled with the design airflow rate, and pressure drop at the design airflow rate.
|
§120.1(b)2
|
High-rise residential air ventilation:
Dwelling ventilation rates and indoor air quality aligned with ASHRAE 62.2 with California amendments.
|
§120.1(b)2
|
Central ventilation systems serving multiple dwelling units:
- Ventilation rate in each dwelling unit must be equal to the rate calculated using equation 120.1-B or up to 20% higher.
- System must be balanced for each dwelling unit.
- Tested in accordance with Reference Nonresidential Appendix NA7.18.1
|
§120.1(b)2
|
Kitchen range hoods:
- Minimum airflow of 100 CFM
- Maximum rated sound of 3 sones
- Certified to the home ventilation institute (HVI)
- Tested in accordance with Reference Nonresidential Appendix NA7.18.1
|
§120.1(c)1
|
Nonresidential and hotel/motel air filtration:
- Filters required for both space conditioning and ventilation systems.
- MERV 13 filter.
- 2” depth filter.
- 1” filter if sized according to equation 120.1-A
|
§120.1(c)2
|
Nonresidential and hotel/motel ventilation:
Natural Ventilation:
- Maximum distance from operable opening is based on location, number of opening, and ceiling height.
- Size of opening must be >4% of ventilated floor area.
- Adjoining rooms without outside air openings must have a permanently opened area not less than 8% of the unventilated room floor area but not less than 25 SQFT.
- Must also include ventilation (120.1 (c) 3) unless meeting exceptions.
|
§120.1(c)4
|
Exhaust ventilation:
- New minimum exhaust ventilation rates are listed in Table 120.1-B (aligns with ASHRAE 62.1
|
§120.1(g)
|
New section that limits the recirculation or transfer of air classification of an occupancy
Table 120.1-A, B and C designates the air classification for each occupancy.
|
§120.1(d)3
|
Direct control ventilation (DCV)
DVC is required if the system serving the space (25 or more per 1000 SQFT) has on of the following:
- An air economizer, or
- Modulating outside air control, or
- A design outdoor airflow rate is > 3000 CFM
|
§120.2(e)3
|
- Occupancy sensors are now mandatory for HVAC control.
- System must be placed in occupied standby mode after 5 minutes of vacancy.
- Occupant sensing zone controls tested per NA7.5.17
|
Electrical
|
140.6
|
Indoor lighting power allowances have been reduced by 37% for the Complete Building Method (see Table 140.6-B) and 29% for the Area Category Method (see Table 140.6-C).
|
140.7
|
Outdoor lighting power allowances have been reduced. See Table 141.0-F.
|
141.0(b)2I
|
Indoor alteration requirements have been simplified and consolidated into new Table 141.0-F
|
150.0(n)
|
Gas or propane water heaters installed in new dwelling units shall include a dedicated 120v receptacle fed by a 10/3 with ground “home run” installed within 3’ of the water heater. This installation shall be available to convert to a future 240v heat pump water heater.
|
150.1(c)14
|
All low-rise residential buildings shall have photovoltaic systems installed, sized to an equation provided in section 150.1(c)14. Some exceptions are included.
|
Covered Processes
|
§120.6(7)
|
Refrigeration system acceptance testing.
- Adiabatic condensers shall be tested in accordance with NA7.10.3.3.
- Variable speed compressors shall be tested in accordance with NA7.10.4
|
Commissioning
|
§100.12
|
Demand management requirements updated:
- Must be certified either as open ADR 2.0a or b virtual end node (VEN) or
- Be capable or responding to an open ADR 2.0b VEN
|
§120.1(b)2
|
Ventilation system must be one of the following:
- Balanced ventilation system, or
- Continuously operating supply or exhaust ventilation systems are allowed if the dwelling unit envelope leakage is verified by a HERS Rater to be <_ 0.3 cfm.
|
§120.1(b)2
|
Kitchen range hoods:
- Minimum rated sound of 3 sones
- Certified to the home ventilation institute (HVI)
- Tested in accordance with Reference Nonresidential Appendix NA7.18.1
|
§120.2(e)3
|
Occupancy sensors are now mandatory for HVAC control.
System must be placed in occupied standby mode after 5 minutes of vacancy.
Occupant sensing zone controls tested per NA7.5.17
|
§120.6(7)
|
Refrigeration system acceptance testing.
- Adiabatic condensers shall be tested in accordance with NA7.10.3.3.
- Variable speed compressors shall be tested in accordance with NA7.10.4
|